UPS Battery

Brochure

Kokams K-UPS provides optimal protection against outages for a number of applications including medical, telecom, and data centers. During an outage, our UPS immediately provides battery backup power to protect mission critical information and systems.

KOKAM BATTERY SYSTEM

TECHNICAL OVERVIEW OF OUR LITHIUM ION BATTERY RACK

  • 2 Pole – Ultra High Power

    2 Pole – Ultra High Power

    Item Specification Remarks
    Backup Time Up to 6 minutes
    Model No. 120S 132S 140S 160S
    Configuration 1P30S x 4 1P33S x 4 1P35S x 4 1P32S x 5 Cell: 130255255P (75Ah)
    Installed Energy 33kWh 36kWh 38kWh 44kWh
    Nominal Voltage 444Vdc 488Vdc 518Vdc 592Vdc
    Operating Voltage Range 384 ~ 495Vdc 422 ~ 545Vdc 448 ~ 578Vdc 512 ~ 660Vdc
    Max. Charge Power 66kW 73kW 77kW 88kW @ 2P, 1 Cycle
    Rated Charge Power 33kW 36kW 38kW 44kW @ 1P
    Max. Discharge Power 333kW 366kW 388kW 444kW @ 10P, ≤6 min., 1 Cycle
    Rated Discharge Power 33kW 36kW 38kW 44kW @ 1P
    Dimension (W x D x H) 580 x 740 x 1,960 mm 780 x 676 x 1,900 mm
    Weight (Approx.) 500kg 550kg 600kg 700kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

    Specification

    • Backup Time Up to 6 minutes
    • Model No. 120S
    • Configuration 1P30S x 4
    • Installed Energy 33kWh
    • Nominal Voltage 444Vdc
    • Operating Voltage Range 384 ~ 495Vdc
    • Max. Charge Power 66kW
    • Rated Charge Power 33kW
    • Max. Discharge Power 333kW
    • Rated Discharge Power 33kW
    • Dimension (W x D x H) 580 x 740 x 1,960 mm
    • Weight (Approx.) 500kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

  • 2 Pole – High Power Type

    2 Pole – High Power Type

    Item Specification Remarks
    Backup Time 5 to 30 minutes
    Model No. 120S 132S 140S 160S
    Configuration 1P30S x 4 1P33S x 4 1P35S x 4 1P32S x 5 Cell: 120255255G1H (85Ah)
    Installed Energy 37kWh 41kWh 43kWh 50kWh
    Nominal Voltage 441Vdc 485Vdc 515Vdc 588Vdc
    Operating Voltage Range 384 ~ 495Vdc 422 ~ 545Vdc 448 ~ 578Vdc 512 ~ 660Vdc
    Max. Charge Power 75kW 82kW 87kW 100kW @ 2P, 1 Cycle
    Rated Charge Power 37kW 41kW 43kW 50kW @ 1P
    Max. Discharge Power 225kW 247kW 262kW 300kW @ 6P, ≤10 min., 1 Cycle
    Rated Discharge Power 37kW 41kW 43kW 50kW @ 1P
    Dimension (W x D x H) 580 x 740 x 1,960 mm 780 x 676 x 2,237 mm
    Weight (Approx.) 526kg 546kg 562kg 700kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

    Specification

    • Backup Time 5 to 30 minutes
    • Model No. 120S
    • Configuration 1P30S x 4
    • Installed Energy 37kWh
    • Nominal Voltage 441Vdc
    • Operating Voltage Range 384 ~ 495Vdc
    • Max. Charge Power 75kW
    • Rated Charge Power 37kW
    • Max. Discharge Power 225kW
    • Rated Discharge Power 37kW
    • Dimension (W x D x H) 580 x 740 x 1,960 mm
    • Weight (Approx.) 526kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

  • 3 Pole

    3 Pole

    Item Specification Remarks
    Type Ultra High Power High Power
    Backup Time Up to 6 minutes 5 to 30 minutes
    Model No. 66S+66S 60S+60S 66S+66S 100S+100S
    Configuration 1P22S x 6 1P30S x 4 1P33S x 4 1P20S x 10
    Installed Energy 36kWh 37kWh 41kWh 62kWh
    Nominal Voltage 244Vdc 220Vdc 242Vdc 368Vdc
    Operating Voltage Range +/-211 ~ 272Vdc +/-192 ~ 247Vdc +/-211 ~ 272Vdc +/-320 ~ 413Vdc
    Max. Charge Power 73kW 75kW 82kW 125kW @ 2P, 1 Cycle
    Rated Charge Power 36kW 37kW 41kW 62kW @ 1P
    Max. Discharge Power 366kW* 225kW 247kW 375kW @ 6P, ≤10 min., 1 Cycle
    *@ 10P, ≤6 min., 1 Cycle
    Rated Discharge Power 36kW 37kW 41kW 62kW @ 1P
    Dimension (W x D x H) 780 x 676 x 1,900 mm 580 x 740 x 1,960 mm 780 x 676 x 2,237 mm
    Weight (Approx.) 580kg 545kg 565kg 810kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

    Specification

    • Type Ultra High Power
    • Backup Time Up to 6 minutes
    • Model No. 66S+66S
    • Configuration 1P22S x 6
    • Installed Energy 36kWh
    • Nominal Voltage 244Vdc
    • Operating Voltage Range +/-211 ~ 272Vdc
    • Max. Charge Power 73kW
    • Rated Charge Power 36kW
    • Max. Discharge Power 366kW*
    • Rated Discharge Power 36kW
    • Dimension (W x D x H) 780 x 676 x 1,900 mm
    • Weight (Approx.) 580kg

    *The product image is for reference purpose. The actual product may be different (Indicative numbers)
    *Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

ADVANTAGES

CUSTOMIZATION OF PARALLEL CABINET & RACK CONNECTIONS
Kokam K-UPS series provides a modular, easily scalable solution. Kokam batterys unique properties of high energy density and lightweight design allow integration of batteries and UPS providing faster and more reliable field installation and start-up.

- Provides noticeably longer cycle life and higher power density than lead acid batteries
- Minimization of degradation with shallow cycles
- Few open-circuit failure modes during normal operation
- No hydrogen generation
- Integrated monitoring of individual cell’s voltages and temperatures

VRLA (Lead Acid) VS Kokam K-UPS

  1. 1
    High Power 5 times more powerful
    VRLA Kokam K-UPS
    (>10C-Rate)
  2. 2
    Long Cycle life Significantly improved
    cycle life
    VRLA
    (MAX 5 years)
    Other Lithium Batteries
    (MAX 10 years)
    Kokam K-UPS
    (MAX 15 years)
  3. 3
    Light Weight 5 times lighter
    VRLA Kokam K-UPS
  1. 4
    Low Maintenance No Hydrogen gas emissions
    No hydrogen gas emissions results in lower ventilation costs and safer operation when compared to Lead-Acid
  2. 5
    Small Footprint 3.3 times more space efficient
    VRLA Kokam K-UPS
  3. 6
    Wide Temperature range No additional cooling system
    VRLA
    (20~22˚C)
    Kokam K-UPS
    (18~28˚C)

Long Cycle life

Up to 15 years warranty guaranteed (Back Up Time Guarantee)

    1. 1
    2. 2
    3. 3
    4. 4
    5. 5
    VRLA
    1. 1
    2. 2
    3. 3
    4. 4
    5. 5
    6. 6
    7. 7
    8. 8
    9. 9
    10. 10
    Other Lithium Batteries
    1. 0
    2. 1
    3. 2
    4. 3
    5. 4
    6. 5
    7. 6
    8. 7
    9. 8
    10. 9
    11. 10
    12. 11
    13. 12
    14. 13
    15. 14
    16. 15
    Kokam K-UPS

Small Footprint : 40% LESS FOOTPRINT, 5 TIMES LIGHTER

VRLA (Lead Acid)

- 10 Total Rack System Wt. / 66,000 Lbs.
- 400”W x 30”D = 83.3ft²
- 2,250kW / 100ft² = 27.0kW/ft²

60 in200 in
Kokam K-UPS

- 8 Total Rack System Wt. / 13,000 Lbs.
- 280”W x 25”D = 48.6ft²
- 2,250kW / 48.6ft² = 46.3kW/ft²

50 in140 in

K-UPS COMPONENT

2 Pole K-UPS

3 Pole K-UPS

Fire Suppression & Fan Battery Protection Unit (BPU)
-String BMS
- Switch Disconnector
- Fuse
- Contactor
Switched Mode
Power Supply (SMPS)
Battery Module
(incl. Module BMS)
Rack Cover

2 Pole K-UPS

3 Pole K-UPS

Fire Suppression & Fan Battery Protection Unit (BPU)
-String BMS
- Switch Disconnector
- Fuse
- Contactor
Switched Mode
Power Supply (SMPS)
Battery Module
(incl. Module BMS)
Rack Cover
HIGHLY SCALABLE AND CUSTOMIZABLE
Kokams UPS (K-UPS), which is comprised of Kokam’s SLPBs, is lightweight and compact due to its high energy density. It can be placed in small spaces and is easy to maintain due to its convenient accessibility.
Also, when compared to lead acid batteries of the same weight and volume, output performance of Kokam SLPB is significantly higher. Kokams UPS can further be classified into two types of backup power systems : short term (minutes) and long term (hours).
KEY STRENGTHS
  • High Power Output
  • Small Volume Footprint
  • Flexible Design
  • Essential backup power to protect critical information and systems
  • Outstanding safety performance
APPLICATIONS

Installed in various locations to provide emergency back-up power during an outage :

  • - Data center
  • - Financial institution
  • - Semi-conductor factory
  • - Medical facility

CONTACT US

If you are interested in our product, please feel free to contact us

Contact Us