UPS Battery Rack

Contact Us

Kokam UPS battery provides optimal protection against outages for a number of applications including medical, telecom, and data centers. During an outage, our UPS battery immediately provides battery backup power to protect mission critical information and systems.

Kokam UPS Battery Rack 

Model KST040471A14ADC00 KST041485A14ADC00 KST043515A14ADC00 KST050588A15ADC00 KST051607A15ADC00 KST054644A15ADC00 KST041242A14AUZ00 Remark
Backup Time 5 to 30 minutes  
Pole 2 Pole 3 Pole  
Rack Configuration 1P32S X 4 1P33S X 4 1P35S X 4 1P32S X 5 1P33S X 5 1P35S X 5 1P33S X 4  
Type High Power  
Cell Capacity (Ah) 85 85Ah / KCL255085PN0
Installed Energy (kWh) 40.0 41.2 43.7 50.0 51.6 54.7 41.2  
Usable Energy (kWh) 36.8 37.9 40.2 46.0 47.4 50.3 37.9 @ 1P discharge, BOL
Nominal Voltage (Vdc) 471.0 485.7 515.2 588.8 607.2 644.0 ±242.8  
Operating Voltage Range (Vdc) 409.6~528.6 422.4~545.1 448.0~578.2 512.0~660.8 528.0~681.4 560.0~722.7 ±211.2~272.5  
Power (kW) Charging Rated 40.0 41.2 43.7 50.0 51.6 54.7 41.2 1P
Max 80.0 82.5 87.5 100.0 103.2 109.4 82.5 2P
Discharging Rated 40.0 41.2 43.7 50.0 51.6 54.7 41.2 1P
Max 235.5 242.8 257.6 294.4 303.6 322.0 242.8 5.8P, ≤7 min.
Peak 360.3 371.6 394.1 450.4 464.5 492.6 371.6 9P, ≤1 min.
Current (A) Charging Rated 85 1C
Max 170 2C
Discharging Rated 85 1C
Max 500 5.8C, ≤7 min.
Peak 765 9C, ≤1 min.
Dimension (W x D x H mm) 580 x 740 x 1,960 580 x 740 x 2,300 580 x 740 x 1,960 ±5mm
Weight (Approx. kg) 534 542 554 658 668 683 552 ±5%
IP Grade 20  
Cycle Life at 90% DOD ≥6,000 @ 25±3℃, 1C/1C, SOH 70%
Cycle Life at 80% DOD ≥8,000
Certification UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A Cell Level
UN 38.3, CE, IEC 62619 Module Level
CE, IEC 62619, IEC 60730-1 Annex H N/A Rack Level
Compliance RoHS II, REACH  
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration 1P32S X 4
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 40.0
  • Usable Energy (kWh)36.8
  • Nominal Voltage (Vdc) 471.0
  • Operating Voltage Range (Vdc) 409.6~528.6
  • Power (kW) - Charging - Rated40.0
  • Power (kW) - Charging - Max80.0
  • Power (kW) - Discharging - Rated40.0
  • Power (kW) - Discharging - Max235.5
  • Power (kW) - Discharging - Peak360.3
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 1,960
  • Weight (Approx. kg) 534
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration 1P33S X 4
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 41.2
  • Usable Energy (kWh)37.9
  • Nominal Voltage (Vdc) 485.7
  • Operating Voltage Range (Vdc) 422.4~545.1
  • Power (kW) - Charging - Rated41.2
  • Power (kW) - Charging - Max82.5
  • Power (kW) - Discharging - Rated41.2
  • Power (kW) - Discharging - Max242.8
  • Power (kW) - Discharging - Peak371.6
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 1,960
  • Weight (Approx. kg) 542
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration 1P35S X 4
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 43.7
  • Usable Energy (kWh)40.2
  • Nominal Voltage (Vdc) 515.2
  • Operating Voltage Range (Vdc) 448.0~578.2
  • Power (kW) - Charging - Rated43.7
  • Power (kW) - Charging - Max87.5
  • Power (kW) - Discharging - Rated43.7
  • Power (kW) - Discharging - Max257.6
  • Power (kW) - Discharging - Peak394.1
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 1,960
  • Weight (Approx. kg) 554
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration 1P32S X 5
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 50.0
  • Usable Energy (kWh) 46.0
  • Nominal Voltage (Vdc) 588.8
  • Operating Voltage Range (Vdc) 512.0~660.8
  • Power (kW) - Charging - Rated50.0
  • Power (kW) - Charging - Max100.0
  • Power (kW) - Discharging - Rated50.0
  • Power (kW) - Discharging - Max294.4
  • Power (kW) - Discharging - Peak450.4
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 2,300
  • Weight (Approx. kg) 658
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration 1P33S X 5
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 51.6
  • Usable Energy (kWh) 47.4
  • Nominal Voltage (Vdc) 607.2
  • Operating Voltage Range (Vdc) 528.0~681.4
  • Power (kW) - Charging - Rated 51.6
  • Power (kW) - Charging - Max 103.2
  • Power (kW) - Discharging - Rated 51.6
  • Power (kW) - Discharging - Max 303.6
  • Power (kW) - Discharging - Peak 464.5
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 2,300
  • Weight (Approx. kg) 668
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 2 Pole
  • Rack Configuration1P35S X 5
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 54.7
  • Usable Energy (kWh) 50.3
  • Nominal Voltage (Vdc) 644.0
  • Operating Voltage Range (Vdc) 560.0~722.7
  • Power (kW) - Charging - Rated 54.7
  • Power (kW) - Charging - Max 109.4
  • Power (kW) - Discharging - Rated 54.7
  • Power (kW) - Discharging - Max 322.0
  • Power (kW) - Discharging - Peak 492.6
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 2,300
  • Weight (Approx. kg) 668
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 CE, IEC 62619, IEC 60730-1 Annex H
  • Compliance RoHS II, REACH
  • Backup Time 5 to 30 minutes
  • Pole 3 Pole
  • Rack Configuration 1P33S X 4
  • Type High Power
  • Cell Capacity (Ah) 85
  • Installed Energy (kWh) 41.2
  • Usable Energy (kWh) 37.9
  • Nominal Voltage (Vdc) ±242.8
  • Operating Voltage Range (Vdc) ±211.2~272.5
  • Power (kW) - Charging - Rated 41.2
  • Power (kW) - Charging - Max 82.5
  • Power (kW) - Discharging - Rated 41.2
  • Power (kW) - Discharging - Max 242.8
  • Power (kW) - Discharging - Peak 371.6
  • Current (A) - Charging - Rated85
  • Current (A) - Charging - Max170
  • Current (A) - Discharging - Rated85
  • Current (A) - Discharging - Max500
  • Current (A) - Discharging - Peak765
  • Dimension (W x D x H mm) 580 x 740 x 1,960
  • Weight (Approx. kg) 552
  • IP Grade 20
  • Cycle Life at 90% DOD ≥6,000
  • Cycle Life at 80% DOD ≥8,000
  • Certification1 UN 38.3, UL1642, UL 1973, IEC 62619, UL 9540A
  • Certification2 UN 38.3, CE, IEC 62619
  • Certification3 N/A
  • Compliance RoHS II, REACH
  • Cell Capacity (Ah) 85Ah / KCL255085PN0
  • Usable Energy (kWh) @ 1P discharge, BOL
  • Power (kW) - Charging - Rated 1P
  • Power (kW) - Charging - Max 2P
  • Power (kW) - Discharging - Rated 1P
  • Power (kW) - Discharging - Max 5.8P, ≤7 min.
  • Power (kW) - Discharging - Peak 9P, ≤1 min.
  • Current (A) - Charging - Rated1C
  • Current (A) - Charging - Max2C
  • Current (A) - Discharging - Rated1C
  • Current (A) - Discharging - Max5.8C, ≤7 min.
  • Current (A) - Discharging - Peak9C, ≤1 min.
  • Dimension (W x D x H mm) ±5mm
  • Weight (Approx. kg) ±5%
  • Cycle Life at 90% DOD@ 25±3℃, 1C/1C, SOH 70%
  • Cycle Life at 80% DOD@ 25±3℃, 1C/1C, SOH 70%
  • Certification1 Cell Level
  • Certification2 Module Level
  • Certification3 Rack Level

* The product image is for reference purpose. The actual product may be different (Indicative numbers)
* Kokam makes no warranty explicit or implied with these specifications. The contents are subjected to change without prior notice.

ADVANTAGES

CUSTOMIZATION OF PARALLEL CABINET & RACK CONNECTIONS

Kokam UPS battery series provides a modular, easily scalable solution. Kokam batterys unique properties of high energy density and lightweight design allow integration of batteries and UPS battery providing faster and more reliable field installation and start-up.
  • Provides noticeably longer cycle life and higher power density than lead acid batteries
  • Minimization of degradation with shallow cycles
  • Few open-circuit failure modes during normal operation
  • No hydrogen generation
  • Integrated monitoring of individual cell’s voltages and temperatures

VRLA (Lead Acid) VS Kokam UPS Battery

  • High Power

    5 times more powerful

    VRLA

    Kokam UPS
    battery
    (>10C-Rate)

  • UPS Battery Cycle life

    Significantly improved cycle life
    UPS Battery Cycle life

    VRLA
    (MAX 5 years)

    Other Lithium Batteries
    (MAX 10 years)

    Kokam UPS Battery
    (Max 15 years)

  • Light Weight

    5 times lighter
    Light Weight

    VRLA

    Kokam UPS Battery

  • Low Maintenance

    No Hydrogen gas emissions
    No hydrogen gas emissions reduce ventilation costs and enable safe operation.
  • Small Footprint

    3.3 times more space efficient
    Small Footprint

    VRLA

    Kokam UPS Battery

  • Wide Temperature range

    No additional cooling system
    Wide Temperature range

    VRLA
    (20~22˚C)

    Kokam UPS Battery
    (22~28˚C)

UPS Battery Cycle life

Up to 15 years warranty guaranteed (Back Up Time Guarantee)


    1. 1
    2. 2
    3. 3
    4. 4
    5. 5

    Years

    VRLA
    1. 1
    2. 2
    3. 3
    4. 4
    5. 5
    6. 6
    7. 7
    8. 8
    9. 9
    10. 10

    Years

    Other Lithium
    Batteries
    1. 1
    2. 2
    3. 3
    4. 4
    5. 5
    6. 6
    7. 7
    8. 8
    9. 9
    10. 10
    11. 11
    12. 12
    13. 13
    14. 14
    15. 15

    Years

    Kokam UPS
    Battery

Small Footprint : 40% LESS FOOTPRINT, 5 TIMES LIGHTER

HIGHLY SCALABLE

AND CUSTOMIZABLE

Kokam’s UPS battery, which is comprised of Kokam’s battery cells, is lightweight and compact due to its high energy density. It can be placed in small spaces and is easy to maintain due to its convenient accessibility. 

Also, when compared to lead acid batteries of the same weight and volume, output performance of Kokam's battery cells is significantly higher. Kokams UPS battery can further be classified into two types of backup power systems : short term (minutes) and long term (hours).

KEY STRENGTHS

  • High Power Output
  • Small Volume Footprint
  • Flexible Design
  • Essential backup power to protect critical information and systems
  • Outstanding safety performance

APPLICATIONS

Installed in various locations to provide emergency back-up power during an outage
  • Data center
  • Financial institution
  • Semi-conductor factory
  • Medical facility

Contact Us

If you are interested in our product, please feel free to contact us